Chapter 6: Plumbing Elements and Facilities Bathing Rooms Size and Clearance 60” min The compartment size and the required clearance adjacent to the open face of the compartment permit maneuvering into the shower with shower chairs or wheelchairs. The clearance must abut, or be close to, the shower entry but may be slightly forward of the shower to accomodate tile edges or flanges around the face of prefabricated showers. 60” min Grab Bars Grab bars are required on three walls in standard compartments without a seat. Grab bars can be continuous or separate. If separate, they must be 6” maximum from adjacent walls and each must be at the same height above the finish floor. The grab bars must extend across the side wall to the entry. A maximum distance of the grab bar from the shower entry is not specified, but they are to be installed near the entry. 5 nim ”03 nim ”03 Note: Dimensions measured to the center point (vertical and horizontal) of opposing walls. A compliant lavatory can overlap one end of the clearance but cannot be adjacent to controls (or a folding seat). ”63 - ”33 6” max 6” max 48” min Note: Grab bar to extend to shower entry (distance from entry not specified) xam ”6 xam ”6

Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.