Toilet rooms: fixture and transfer clearances

Toilet-room layouts, water-closet transfer spaces, grab bars, lavatories and accessible toilet compartments.

AccessibilityAnthropometry & ergonomics
Open original PDF at page 31

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

Chapter 6: Plumbing Elements and Facilities Toilet Rooms Urinals [§213.3.3, §605] At least one urinal must comply where two or more urinals are provided in a toilet room. Specifications address rim height, depth, flush controls, and clear floor space. Accessible urinals must be either wall hung or stall type. Flush controls must be automatic or, if hand operated, compliant as operable parts and located within accessible reach range (§309). Wall Hung Urinal Stall Type Urinal 13½” min 31 xam ”71 Clear floor space for a forward approach is required. Partitions or privacy panels cannot obstruct or reduce the minimum clearance. If partitions or panels obstruct both sides of the clear floor space for more than 24”, the clear floor space must be at least 36” wide instead of 30” wide. X Portions of wall hung urinals that provide toe clearance (9” high min.) 30” min can overlap the clear floor (36” min if space for a depth of 6” max. X>24”) 48” min

Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.