Chapter 6: Plumbing Elements and Facilities Toilet Rooms
Compartment doors must meet maneuvering clearance requirements, but a reduced clearance
is specified for compartment doors providing a latch approach. Doors can be hinged on either
side.
Recommendation: Hinging doors to provide a latch approach instead of a hinge
approach will provide easier access and require less maneuvering clearance.
Latch Approach Clearance Forward Approach Clearance
26
nim
”24
24” min 18” min nim
”06
Alternative Hinge
Hinge Approach Clearance
Approach Clearance
36” min
nim
”06
42” min nim
”45